The PLC CPU operation speed reaches the highest standard in the industry 0.06μs (Boolean operation instructions). RPC2117N integrates with 14 24VDC 16 channel I/O, DI 10×DC24V, DO 6× relay, rated working voltage of 220VAC, support photoelectric isolation, 16-bit counter unlimited point.
CPU performance
I/O channel:10 channels of 24VDC input and 6 channels of relay output.
Extension ability: Up to 25 modules can be extended (if more than 8 modules are extended, RPA002 extention set of relay module is required).
Storage capacity: Program area 256K bytes;
the data is 42k bytes in N area and 16kbytes in M area.
Power-down holding area 3kbytes
Timer: Software timing is unlimited (minimum unit is 1ms)
Counter: 16 digits, unlimited.
Arithmetic speed 0.06μs (Boolean operation instruction).
Input channel
Input type: Drain/source type
input signal: Rated voltage 24VDC
Allowable range 0~30VDC
Input ON signal: 15~30VDC, allowing a minimum current of 3mA.
Input OFF signal: 0~5VDC, maximum allowable current is 1mA.
Input delay: < 0.6ms (rated input voltage)
Isolation mode: Photoelectric isolation
Isolation withstand voltage : 1000VDC
Output channel
Output type: relay
Output voltage: 24VDC or 24~230VAC
Allowable range: 5~30VDC or 5~250VAC
Sum of common terminal output currents: <5A
Output contact capacity: 2A, resistive load
Switching delay: <10ms
Isolation voltage between coil and contact: 3000VAC,1 minute, 1mA leakage current.
Isolation voltage between contacts: 750VAC,1 minute, leakage current 1mA.
Mechanical life of relay: When there is no load, it can reach more than 10,000,000 times,It can reach more than 100,000 times under rated resistive 2A load.
Communication characteristics
communication interface: 1 RS232,2 RS485
1 RJ45 Ethernet (program download interface)
Protocol Serial port: MODBUS RTU protocol, free protocol
Network port: MODBUS TCP protocol, UDP protocol.
Power supply parameters
Power supply voltage: 220VAC @50Hz
Allowable range: 187~264VAC @50Hz
maximum current : 120mA
Output voltage (terminal VO+ VO-): Rated at 24VDC, the allowable range is 22.8~25.2VDC.
Output current (terminal VO+ VO-): 400mA (isolated from internal power supply and withstand voltage of 1000VDC)
Short circuit protection: 800mA,24VDC output
Working environment
Working temperature: 0~60℃
Storage temperature: -40~70℃
relative humidity: 5~95% (no condensation)
Shape and installation
Dimensions:120mm(L)×80mm(W)×63mm(H)
Weight:380g
Installation mode: Guide rail installation, standard 35mm DIN guide rail, Panel installation
RPC2117N Programmable logic controller PLC module with 16 channel I/O
16 channel I/O, DI 10×DC24V, DO 6× relay;
1 RS232;
2 RS485(isolation);
1 Ethernet;
AC220V power supply;